JT6200T Series Single‑Phase True RMS Multifunction Power Meter
1. Product Overview
JT6200T series is professional single‑phase multifunction panel meter. It adopts 24‑bit AD chip and true RMS algorithm for accurate measurement under distorted waveform.
It supports AC/DC measurement, measuring range expandable by voltage transformers, current transformers, shunts or Hall sensors. This meter integrates real‑time monitoring, energy accumulation, limit alarm, analog retransmission and Modbus communication in compact DIN panel structure. Multiple housing sizes and power supply options satisfy automation, heat‑treatment and new‑energy industry requirements.
2. Core Functions
● Comprehensive electrical measurement: Measure AC/DC voltage, current, active power, frequency; support electric energy accumulation. True RMS calculation keeps accuracy for non‑sinusoidal loads.
● 2‑channel relay alarm output: Support upper‑limit, lower‑limit and deviation alarm, adjustable hysteresis and delay.
● 2‑channel isolated analog transmitter output: Configurable 0‑20mA,4‑20mA,0‑5V,0‑10V for remote signal transmission.
● Opto‑isolated RS485 Modbus RTU: Connect to PLC,HMI,SCADA; adjustable address, baud rate and parity.
● Adjustable digital filtering: Suppress noise to avoid value flickering; support zero offset calibration.
● LCD display with touch keys: Multi‑page data display for measurement, alarm log and parameter setup.
3. Key Features
● Measurement accuracy: ≤0.2% FS, 24‑bit high‑speed AD sampling
● AC and DC hardware versions (please specify when ordering)
● Wide measuring range, expandable via CT / VT / shunt / Hall sensor
● 2000V isolation between input, output and communication ports
● Standard DIN panel sizes:96×96mm,96×48mm,48×96mm
● Auxiliary power: AC90‑260V or DC24V
● Low power consumption: Max 4W, working temperature:0~50℃
● CE & RoHS compliant, suitable for long‑term cabinet‑mount operation
4. Main Technical Parameters
Accuracy: ≤0.2%FS
AD Resolution: 24‑bit
Auxiliary Power: AC90‑260V / DC24V
Relay Contact Rating: 2A/250VAC
Communication: Isolated RS485, Modbus RTU
Analog Output: 2‑channel isolated transmitter
Isolation Voltage: 2000V AC
Working Temperature: 0~50℃
5. Application Scenarios
● New‑energy: photovoltaic equipment, new‑energy vehicle test bench
● Thermal treatment: mesh‑belt furnace, carburizing furnace control cabinet
● Industrial automation: PLC panel, welding & packaging machinery
● Power distribution: low‑voltage cabinet, UPS power monitoring
● Laboratory test equipment: power aging test stands
6. Order Notice
1. AC and DC models use different hardware, please mark input type when ordering.
2. Specify measuring range, transformer/shunt requirement.
3. Confirm auxiliary power supply type and panel dimension.
| Model | JT6204A/JT62H8A/JT6208A; JT6204D/JT62H8D/JT6208D |
| Measurement Accuracy | < 0.2% |
| AC Measurement AD Accuracy | 24-bit AD |
| Voltage Range | AC500V; DC1000V |
| Current Range | AC5A; DC75mV, DC5V |
| High-voltage Power Supply Range | AC90-260V / DC110-380V |
| DC Low-voltage Power Supply Range | DC24V±10% |
| Maximum Power Consumption | 4W |
| Operating Environment | 0~+50°C; ≤85%RH |
| Relay Contact Capacity | 2A 250VAC |
| Relay Contact Life | 100,000 times |
| Transmitter Output Accuracy | 16-bit |
| Input/Output Isolation Voltage | 2000V AC |
| Isolation Voltage Between Two DA Channels | 2000V AC |
| Isolation Voltage Between Input Voltage and Input Current | 2000V AC |
| Maximum Display Range | 99999999.99 (for electrical energy measurement) |
| Communication | Optically isolated RS-485 communication interface |
| Overall Dimensions | 96x96x130mm / 48x96x130mm / 96x48x130mm |
| Cutout Dimensions | 92x92mm / 45x92mm / 92x45mm |
Hot Tags: Single-phase multifunction power meter, China Single-phase multifunction power meter manufacturers, suppliers, factory, True RMS Multifunctional Meter with Communication, 3PH True RMS Multifunctional Power Meter, True RMS Measurement Voltage and Current Meter, multifunctional power meters, Multifunctional Power Meter with Expandable Range, Intelligent Voltage and Current Meter