What is Main Control Output

The main control output is the core output of the temperature controller, used to directly control the load. Its purpose is to stabilize the temperature at the set value, and it belongs to the closed-loop control execution terminal.

Common types

Relay contact output (passive dry contact, for controlling contactors and fans)

SSR drive output (for driving solid state relays)

Thyristor trigger output

Analog regulating output: 0-10V / 4-20mA

Main features

Directly control heating, cooling and actuator equipment

Realize PID automatic regulation according to temperature deviation

Target loads: contactors, solid state relays, power regulators

Belongs to control output, responsible for on-site temperature regulation

What is Transmission Output

Transmission output, also called analog retransmission output, converts the actual measured temperature into standard industrial analog signals for remote transmission.

Common signal types

4-20mA / 0-20mA / 0-10V / 0-5V

Main features

Used for temperature data uploading and remote monitoring

Output signal changes linearly with actual temperature

Connected to PLC, HMI, recorder, data acquisition module and host computer

Belongs to signal transmission output, only for data collection, not participating in on-site control

Comparison: Main Control Output vs Transmission Output

表格

Item Main Control Output Transmission Output
Function Control load and regulate temperature Remote temperature signal transmission & data collection
Working logic PID adjustment / on-off control Linear follow actual temperature
Connected device Contactor, SSR, power regulator PLC, HMI, recorder, upper computer
Signal type Relay contact / SSR pulse / analog regulation Standard 4-20mA / 0-10V analog signal
Control participation Directly involved in temperature closed-loop control Only data transmission, no control function
Application On-site local temperature control Centralized monitoring and remote acquisition

Application Scenarios

Only Main Control OutputIndependent ovens, electric furnaces and standalone heating equipment; only local constant temperature control is required, no data upload needed.

Only Transmission OutputNo direct load control on site; temperature signal is sent to PLC or upper computer for unified system logic control.

Dual Output Used Together (Most Common)

Main control output: Realize precise local constant temperature by controlling heating/cooling loads

Transmission output: Transmit real-time temperature to PLC, touch screen and recorder for remote viewing, data recording and system interlock

Selection & Wiring Notes

If you need to control heating loads, choose a model with main control output.

If temperature data needs to be uploaded to PLC or host computer, please select transmission output.

Transmission output is active analog signal; please pay attention to positive / negative polarity and use shielded cable for long distance.

Relay main control output is passive dry contact, no polarity requirement, external power supply is needed to form a loop.

Do not mix the two outputs; wrong connection may damage the instrument port.

Summary

Main Control Output - Controls the load and keeps temperature stable locally.

Transmission Output - Transmits real-time temperature signal remotely for monitoring and data recording.

Reasonable matching of both outputs realizes precise local temperature control as well as remote monitoring and automatic system linkage.